Troubleshooting Trees
Page C3
Machine Does Not Run
Check for correct
power supply to the
machine
YES NOT OK
NO
OK
Is the selector
switch set to
ICE?
Check High
Pressure Safety
Control
Check High
Temperature Safety
Control
OK
Check Bin Control
for proper
adjustment, see
page F9
Is this a Remote
unit?
Is the Liquid line
Solenoid energized
and open?
OK
OK
GOOD
TRIPPED
OPEN
BAD
NO
NOT O
K
O
K
Adjust as
required or
replace if
defective
Replace or
identify reason
for being open.
Reset and
identify reason
for high head
pressure
Correct field
wiring deficiency
Set selector
Switch to the
ICE position
Selector Switch
could be
defective, see
page F1
Find reason for
non-activity or
replace if
defective