I-Series Ice Machine Training Manual
© 2001, IMI Cornelius Inc.
- 21 -
D14 Green LED
ON 15
seconds
Water pump active for 15 sec., then inactive
D15 Green LED ON
Compressor contactor closed (compressor
active)
D16 Green LED
ON 15
seconds
Dump valve active 15 sec.
Error-LEDs
D9 Red LED Turns on when the system is shutdown
D9 Red LED
ON or
flashing
Assists to indicate where the error may be
and or what may have caused the error
D9 Red LED ON
Evaporator temp. drops below -25° F
(-32° C) – the system will shutdown for 30
min’s and attempt to restart 2 times before
shutting down
D9 Red LED ON
Open thermistor circuit – thermistor open/
broken or wire/poor connector
D9 Red LED ON
High evaporator temperature – evaporator
does not fall below 40° F (4° C) within 6
minutes into freeze cycle – requires manual
reset
D9 Red LED ON 3 failed harvest cycles (when no ice drops)
D9 Red LED
Flashing
1/2 sec.
ON, 1/2
sec. OFF
Open sensor or high temperature shutdown
– condenser temp. exceeds 150° F +2°, -6°
(66° C +1°, -3°) – the system will shutdown
for 30 min’s and attempt to restart 2 times
before shutting down
D9 Red LED
Flashing
1/4 sec.
ON, 1/4
sec. OFF,
1 sec.
delay,
then
repeat
Low temperature shutdown – condenser
temp. drops to 36° F ±2° (2° C ±1°) – the
ice machine will restart if temp. rises to
40° F ±2° F (1° C)
D9 Red LED
Flashing
1/4 sec.
ON, 1/4
sec. OFF,
Within one turn of either end of the potenti-
ometer range
SERVICE