I-Series Ice Machine Training Manual
© 2001, IMI Cornelius Inc.
- 5 -
3. OVERVIEW
3.1 Product Description
The normal sequence of events for starting the I-Series Ice Machine is as follows:
1. The ON-OFF-CLEAN switch is switched ON.
2. Controller board does a startup check.
3. After 4 seconds the contactor closes and the compressor starts.
4. When the condenser thermistor reaches 100° F (38° C), the fan starts. The fan
stops when the thermistor drops to 88° F (31° C).
5. When the suction line thermistor reaches 20° F (-7° C), the water pump starts.
Ice Machine
Ice Bin
ON/OFF/CLEAN and
DUMP switches
INTRODUCTION