DUMP CYCLE
1. With the proper water level in the water pan, start the water
pump to circulate the water. Check that the float will return
water level to original setting and stop the inlet water.
2. There is flow washer in the inlet side of the float assembly that
will control inlet eater pressure from 50/120 PSI (3.4/8.16 Bars). This
will prevent float flutter. In low water pressure conditions, 20 PSI
(1.37 Bars) or less, the flow washer may have to be removed from
the float assembly for proper fill volume.
FLOW CONTROL WASHER
FLAT SIDE UP
FIGURE 5. FLOW CONTROL WASHER
Push the manual DUMP switch - allow dump action to drain the water pan. When you release the momentary
switch, the pump will stop and the float will return the water level back to its original setting and shut off the wa-
ter supply.
3. You have the option of selecting dump cycle intervals of:
S every cycle
S every 3rd cycle
S every 7th cycle
Remember: The higher the mineral content in the water supply the more often it will be required to dump the
water and/or clean the product if proper water treatment is not used.
OPERATING WATER LEVEL
SINGLE EVAPORATOR
1.5”
WATER PAN RIGHT SIDE VIEW